EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-3031 - Figure 2.10 SEL-C387 Cable: SEL-3031 to SEL Communications Processor; Figure 2.11 SEL-C273 A Cable: SEL-3031 Repeater and Synchronizing

Schweitzer Engineering Laboratories SEL-3031
122 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SEL-3031 Instruction Manual Date Code 20181001
Installation
Communications
2.20
CAUTION
You must turn off the +5 V on Pin 1 of the SEL-3031 when connecting to a communications processor.
Figure 2.10 SEL-C387 Cable: SEL-3031 to SEL Communications Processor
With IRIG-B
Figure 2.11 SEL-C273A Cable: SEL-3031 Repeater and Synchronizing Cable
SEL-3031
9-Pin Male
Subminiature "D" Connector
With IRIG
9-Pin Male
Subminiature "D" Connector
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
Pin # Pin #
NOTE: For best results, limit the cable length to 15 m (~50 ft)
SEL Communications Processor
SEL-3031
9-Pin Male
"D" SUB CONNECTOR
DB-9-P
9-Pin Male
"D" SUB CONNECTOR
DB-9-P
2
3
5
7
8
3
2
5
8
7
RXD
TXD
GND
SYNC IN
SYNC OUT
SHELL
Pin
Func.
RXD
TXD
GND
SYNC IN
SYNC OUT
NO CONNECTION
Pin
Func.
Pin # Pin #
SEL-3031
CABLE: 9 Conductor 22 AWG 7/30 Tinned Copper with PVC Jacket
(Shielded: Alpha 1298C or equal; Unshielded: Alpha 1179 or equal)
ORANGE
RED
BLUE/SHIELD
GREEN
WHITE
SHIELD
Preliminary Copy—Subject to Change

Table of Contents