Date Code 20181001 SEL-3031 Instruction Manual
Performance Monitoring, Testing, and Troubleshooting
Troubleshooting
5.7
Cannot change radio set-
tings.
Invalid password. Install password disable jumper
and change passwords using
the PAS command. See Pass-
word Jumper on page 2.14 for
information on how to disable
passwords.
Wall-mount radio will not
turn on.
The polarity of the power
supply wires is reversed.
Check the correct polarity and
reverse if incorrect.
The remote radio will not
link up to the master.
Radio address or mode is
not set correctly.
The master and remote radios
must be set to the same address
and have the same SKIP set-
tings. Check that the master
radio LINK light is ON and that
the NID address and SKIP set-
ting is set correctly on both
units.
Antennas are not pointed
correctly, or there is a bad
antenna cable.
Use QuickSet on the radio to
issue the RAD command to
check for signal strength. If the
signal is low, try to re-aim both
antennas to gain signal strength
and check for bad antenna
cables. See Section 2: Installa-
tion for more information on
proper radio installation.