SEA SYSTEMS
INSTALLATION AND USE MANUAL
CONTROL PANEL and PREWIRED SYSTEM STK1
For Electric and Hydraulic Lifts
MSTK12-GB
Rev.01
30/12/05
SETRONIK1 Pagina 46 di 54
LED CARD PORT
TYPE
STATUS DESCRIPTION
OCC STK1-B OUT_NP ON
Flashing
Car occupied at floor
Car moving
PCP STK1-B IN_NP ON Door closing pushbutton closed
PS1..
PS6
STK1-B OUT_NP ON Car position
PS7..
PS12
STK1-E OUT_NP ON Car position
PST STK1-B IN_P ON Low and peak point pressure switch closed (hydr)
(N.C. contact)
S STK1-B IN_NP ON
Upward contactor (KS) \ Y\ contactor closed
SCE STK1-B OUT_NP ON Overloaded car
SGG STK1-B OUT_NP ON Gong actived
SR STK1-B IN_NP OFF SR sensor contact open (car at the top)
TC STK1-B IN_P ON Oil thermostat closed (hydraulic) (N.C. contact)
X1 STK1-B IN_P ON It is matched to the programmable input X1 (*)
X10 STK1-B IN_P ON Additional sensor IS closed (with very close floors)
X11 STK1-B IN_P ON Additional sensor ID closed (with very close floors)
X2, X3,
X4, X5
STK1-E IN_P ON They are matched to the programmable inputs X2,
X3, X4, X5 (*)
X6 STK1-B IN_P ON Opening\closing contactor closed (KAP\KCP) (1st
operator)
X7 STK1-E IN_P ON Opening\closing contactor closed (KAP1\KCP1) (2nd
operator)
X8 STK1-B IN_P ON Safety circuit closed (car at floor)
X9 STK1-B IN_P ON It is matched to the programmable input X9 (*)
OUT_NP = No programmable output
OUT_P = Programmable Output (*)
IN_NP = No programmable Input
IN_P = Programmable Input (*)
(*) = The programmed function code is specified on the tab TS01, the programmed
function is described at the paragraphs 2.14 and 2.15.