INSTALLATION AND USE MANUAL
CONTROL PANEL and PREWIRED SYSTEM STK1
For Electric and Hydraulic Lifts
MSTK12-GB
Rev.01
30/12/05
SETRONIK1 Pagina 49 di 54
CODE DESCRIPTION
100..123 Sensor IS skipped a Stop plate during the upward run
(skipped floor = ‘Error code’ less 99)
124..147 Sensor ID skipped a Stop plate during the downward run
(skipped floor = ‘Error code’ less 123 )
148..171 Sensor IS skipped a Speed change plate during downward run
(Related floor = ‘Error code’ less 147 )
172..195 Sensor IS skipped a Speed change plate during upward run
(Related floor = ‘Error code’ less 171 )
196..219 Sensor ID skipped a Speed change plate during downward run
(Related floor = ‘Error code’ less 195 )
220..243 Sensor ID skipped a Speed change plate during upward run
(Related floor = ‘Error code’ less 219 )
244 Sensor DR open at the upper floors in run
245 Sensor DR closed with car in floor zone at the upper floor, or
Sensor DR open with car in floor zone at the lower floors
246 Sensor SR closed with car in floor zone at the lower floor, or
Sensor SR open with car in floor zone at the upper floors
247 Sensor SR open at the lower floors at start
248 Sensor DR and SR open simultaneously_ Temporary Out of Order at floor