Operation planning
4.1 Operation planning
SENTRON PAC4200
System Manual, 09/2009, A5E02316180B-02
65
Circuit breaker
A suitable circuit breaker must be connected upstream of SENTRON PAC4200 in order to
permit disconnection of the device from the power supply.
The circuit breaker must be mounted close to the device and be easily accessible to the
user.
The circuit breaker must be marked as the circuit breaker for the device.
Temperature compensation
To avoid condensation, the device must be stored at the operating location for at least 2
hours before power is connected.