EasyManua.ls Logo

Shark MP200 - Page 447

Shark MP200
496 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D: MP200-S (Single Phase) Modbus Map
Doc# E166703 D-119
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description Format Range Units or Resolution Comments # Reg
Modbus Address
Hex Decimal
7D21 - 7D21 32034 - 32034 Input Accumulators Scaling UINT16 bit-mapped
44443333 22221111
1
7D22 - 7D22 32035 - 32035 Relay Accumulators Scaling UINT16 bit-mapped
44443333 22221111
1
7D23 - 7D3E 32037 - 32063 Reserved Set to 0. 8
7D3F - 7D46 32064 - 32071 Input#1 Label ASCII 16 char 8
7D47 - 7D4E 32072 - 32079 Input#1 Low State Name ASCII 16 char 8
7D4F - 7D56 32080 - 32087 Input#1 High State Name ASCII 16 char 8
7D57 - 7D6E 32088 - 32111 Input#2 Label and State Names 24
7D6F - 7D86 32112 - 32135 Input#3 Label and State Names 24
7D87 - 7D9E 32136 - 32159 Input#4 Label and State Names 24
7D9F - 7DA6 32160 - 32167 Relay#1 Label ASCII 16 char 8
7DA7 - 7DAE 32168 - 32175 Relay#1 Open State Name ASCII 16 char 8
7DAF - 7DB6 32176 - 32183 Relay#1 Closed State Name ASCII 16 char 8
7DB7 - 7DCE 32184 - 32207 Relay#2 Label and State Names 24
7DCF - 7DFE 32208 - 32255 Reserved Reserved 48
7DFF - 7E06 32256 - 32263 Input#1 Accumulator Label ASCII 16 char 8
7E07 - 7E0E 32264 - 32271 Input#2 Accumulator Label ASCII 16 char 8
7E0F - 7E14 32272 - 32277 Input#3 Accumulator Label ASCII 16 char 8
7E15 7E1E 32278 32287 Input#4 Accumulator Label ASCII 16 char 8
7E1F - 7E1F 32288 - 32288 Input#1 Accumulator Kt UINT16 bit-mapped
ddVVVVVV VVVVVVVV
1
7E20 7E20 32289 32289 Input#2 Accumulator Kt UINT16 bit-mapped
ddVVVVVV VVVVVVVV
1
KT power factor for the Pulse Output
"V" is raw power value in Wh/pulse
from 0 to 9999. "dd"=decimal point
position: 00=0.XXXX, 01=X.XXX,
10=XX.XX, 11= X.XXX.
same as Input#1
same as Inp
ut#1
same as Input#1
same as Relay#1
4 bits per input or output
accumulator
The nibble informs what should be
the scaling of the accumulator 0=no-
scaling, 1=0.1, 2=0.01, 3= 1m,
4=0.1m, 5=0.01m, 6=1u, 7=0.1u; the
value 15 disable the accumulator.
Example: suppose that the internal
input accumulator #1 is 12345, and
its corresponding scaling setting is
ā€œ0011ā€ (3 decimal). Then, the
accumulator will be read as:
Scaling 3, means 1m or 0.001.
Scaled accumulator = 12345 * 0.001
= 12 (Twelve).

Table of Contents