Doc# E166703 4-8
4: Electrical Installation
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
ings. CT polarities are dependent upon correct connection of CT leads and the direc-
tion CTs are facing when clamped around the conductors.
EIG recommande fortement d'utiliser les blocs de court-circuit pour permettre le
retrait de l'unité MP200 d'un circuit sous tension, si nécessaire (voir Section 4.7 pour
les instructions). EIG recommande l'aide d'un bloc de court-circuit triphasé pour
chaque charge en trois phases. Un exemple de ce bloc de court-circuit est le EI SB-
6TC, figurant sur la page suivante. Il peut être commandé à partir de notre site Web :
www.electroind.com. Vous aurez besoin de huit blocs de court-circuit pour les huit cir-
cuits triphasés. Les blocs de court-circuit vous permettent de court-circuiter un trans-
formateur de courant installé de telle sorte que le compteur peut être désinstallé, si
nécessaire, pour l'entretien. C'est une fonction sécuritaire très importante.
4.6: Electrical Connection Diagrams
The following pages contain electrical connection diagrams for the MP200 unit’s
meters, which now support Delta connections as well as Wye. Choose the diagram
that best suits your application. Be sure to maintain the CT polarity when wiring.
The diagrams are presented in the following order:
1. Three Phase, 4-Wire Wye Service with Direct Voltage and 3 CT Connection for
Metering 8 Three Phase Loads (MP200-Y)
2. Three-Phase, 4-Wire Wye Service with 3 PT Voltage and 3 CT Connection for Meter-
ing 8 Three Phase Loads (MP200-Y)
3. Three-Phase, 3-Wire Delta Service with Direct Voltage and 2 CT Connection for
Metering 8 three Phase Loads (MP200-Y)
4. Single Phase, 2-Wire Service with Direct Voltage and 3 CT Connection for Metering
24 Single Phase Loads (MP200-S)
5. Single Phase, 3-Wire Service with Direct Voltage and 2 CT Connection for Metering
8 Single Phase Loads (MP200-S)
6. Single phase, 3-Wire Service with Direct Voltage and 1 CT Connection for Metering
24 Single Phase Loads(MP200-S)
IMPORTANT! Tous les transformateurs de courant doivent avoir un côté à la terre
pour réduire les risques de choc. EIG recommande fortement d'utiliser les blocs de
court-circuit comme le EI SB-6TC de sorte que le compteur peut être retiré de sa
fonction tandis que le transformateur de courant est sous tension.