Doc# E166703 E-22
E: Retrieving Logs
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Enable: 1 (Engage log)
Scope: 0 (Normal Mode)
---------------------------------------------------
Receive: 0106C34F0180 (echo)
NOTE: This engages the log for use on this COM Port, and latches the oldest record as
record index 0.
3. Read [0xC747, 16 registers], Availability is 0.
Send: 0103 C747 0010
Command:
Register Address: 0xC747
# Registers: 16
---------------------------------------------------
Receive: 010320 00000100 00000064 0012 0002
0C0717101511 0C0718101511
0000000000000000
Data:
Max Records: 0x100 = 256 records maximum.
Num Records: 0x64 = 100 records currently logged.
Record Size: 0x12 = 18 bytes per record.
Log Availability: 0x02 = 1, In use by COM2, USB (the current
port)
First Timestamp: 0x0C0717101511 = July 23, 2012, 16:21:17
Last Timestamp: 0x0C0717101511 = July 24, 2012, 16:21:17
NOTE: This indicates that the log has been engaged properly in step 2. Proceed to
retrieve the log.