Doc# E166703 E-24
E: Retrieving Logs
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
5. Read [0xC351, 125 registers], first 2 registers are status/index, last 123 registers
are window data. Status OK.
Send: 0103 C351 007D
Command:
Register Address: 0xC351
# Registers: 0x7D, 125 registers
---------------------------------------------------
Receive: 0103FA 00000000
0C0717101511FFFFFFFFFFFFFFFFFFFFFFFF
0C071710160042FAAACF42FAAD1842FAA9A8. . .
Data:
Window Status: 0x00 = the window is ready.
Index: 0x00 = 0, The window starts with the 0'th record,
which is the oldest record.
Record 0: The next 18 bytes is the 0'th record (filler).
Timestamp: 0x0C0717101511, = July 23, 2012, 16:21:17
Data: This record is the "filler" record. It is used by the
MP200 unit so that there is never 0 records. It
should be ignored. It can be identified by the data
being all 0xFF.
NOTE: Once a log has rolled over, the 0'th record
will be a valid record, and the filler record will
disappear.
Record 1: The next 18 bytes is the 1'st record.
Timestamp: 0x0C0717101600 July 23, 2012, 16:22:00
Data:
Volts AN: 0x42FAAACF, float = 125.33~
Volts BN: 0x42FAAD18, float = 125.33~