Doc# E166703 E-30
E: Retrieving Logs
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
NOTE: The System Log Record is 20 bytes, consisting of the Record Header (12
bytes) and Payload (8 bytes). The Timestamp (6 bytes) is in the header. Typically,
software will retrieve only the timestamp and payload, yielding a 14-byte record. The
table below shows all defined payloads.
Group
(Event
group)
Event
(Event
within
group)
Mod
(Event
modifier)
Channel
(1-3 for
COMs,
0 for FW)
Parm1 Parm2 Parm3 Parm4 Comments
0 Startup
000FW version Meter Run
Firmware
Startup
1 Log Activity
1 log# 1-3 0xFF 0xFF 0xFF 0xFF Reset
2 log# 1-3 0xFF 0xFF 0xFF 0xFF Log Retrieval
Begin
3 log# 0-3 0xFF 0xFF 0xFF 0xFF Log Retrieval
End
2 Clock Activity
1 old year 1-3 old month, day, hour, minute, second Clock Changed
2000xFF0xFF0xFF0xFFDaylight Time
On
3000xFF0xFF0xFF0xFFDaylight Time
Off
3 System Resets
1 0 0-3 0xFF id mm# 0xFF 0xFF Max & Min
Reset
2 0 0-3 0xFF id e# 0xFF 0xFF Energy Reset
3 slot# 0-3 0xFF acc_typ
#
0xFF 0xFF Reset Relay
Board
Accumulators
4 Settings
Activity
1 0 1-3 0xFF 0xFF 0xFF 0xFF Password
Changed
201-3old
V-Switch
new V-
Switch
0xFF 0xFF V-Switch
Changed