Doc# E166703 E-42
E: Retrieving Logs
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Sample Historical Log 1 Record:
Historical Log 1 Record and Programmable Settings
14 0D 01 17 0D 16 15 00 14 0D 01 17 0D 24 00 00
22 00 00 00 0E 00 00 00 00 00 00 00 00 00 |07| 00
DF 7F 05 00 00 00 00 00 00 00 00 00 00 00 00 00
|37| 00 00 00 |01| 00 00 00 00 00 00 00 00 00 00 00
00 00 00..........
|E7 03|04| 00 |0A| 00 00 00 00 00 00 00 00 00 00 00
|E9 03|04 00 |0A| 00 00 00 00 00 00 00 00 00 00 00
|EB 03|04| 00 |0A| 00 00 00 00 00 00 00 00 00 00 00
|ED 03|04| 00 |0A| 00 00 00 00 00 00 00 00 00 00 00
|EF 03|04| 00 |0A| 00 00 00 00 00 00 00 00 00 00 00
|F1 03|04| 00 |0A| 00 00 00 00 00 00 00 00 00 00 00
|F3 03|04| 00 |0A| 00 00 00 00 00 00 00 00 00 00 00
Item values Type and Size Descriptions
07 # registers
37 # sectors
01 interval
E7 03 0A 04 (SINT 2 byte)Voltage A-N
E9 03 0A 04 (SINT 2 byte)Voltage B-N
EB 03 0A 04 (SINT 2 byte)Voltage C-N
ED 03 0A 04 (SINT 2 byte)Voltage A-B
EF 03 0A 04 (SINT 2 byte)Voltage B-C