Name Use Data type Definition Values Safety implica‐
t
ion
NonsafeCutOffPath02
N
onsafeCutOffPath08
Additional func‐
tion
BOOL Cut-off path 02 … 08
(Not safety-related)
The signal is ON if
the currently monitored
field in the cut-off path
is free.
1)
0 = OFF state,
detection in field
Parameter with‐
out safety impli‐
cation
1 = ON state,
f
ield free
ReferenceContourStatus Diagnostics BOOL Reference contour
monit
oring
The safety laser scan‐
ner does not detect any
contour within the con‐
figured tolerance band
of the reference con‐
tour field. All safety out‐
puts in the OFF state.
0 = contour in
the set tolerance
band or refer‐
ence contour
monitoring not
active
Parameter with
implication for
the safety func‐
tion
1 = contour not
in se
t tolerance
band
ResetRequiredCutOffPath01 Diagnostics BOOL Reset required, Cut-off
path 01
Signals whether the
device is waiting for a
reset signal to switch
safety-related cut-off
path 01 to the ON
state.
0 = reset not
required
Parameter with
implication for
the safety func‐
tion
1= reset required
ResetRequiredCutOffPath02
R
esetRequiredCutOffPath08
Diagnostics BOOL Reset required, Cut-off
path 02 … 08
Signals whether the
device is waiting for a
reset signal to switch
the respective safety-
related cut-off path to
the ON state.
1)
0 = reset not
required
Parameter with
implication for
the safety func‐
tion
1= reset required
RunModeactive Diagnostics BOOL Status of safety func‐
t
ion
Signals the operational
status of the device.
0 = safety func‐
tion paused.
Parameter with‐
out safety impli‐
cation
1 = safety func‐
tion is executed.
SafeCutOffPath01 Safety function BOOL Cut-off path 01 (safety-
or
iented)
The signal is ON if
the currently monitored
field in the cut-off path
is safety-related and
free.
0 = OFF state,
detection in pro‐
tective field
Safety-relevant
parameter
1 = ON state,
protective field
free
SafeCutOffPath02
S
afeCutOffPath08
Safety function BOOL Cut-off path 02 … 08
(safety-oriented)
The signal is ON if
the currently monitored
field in the cut-off path
is safety-related and
free.
1)
0 = OFF state,
detection in pro‐
tective field
Safety-relevant
parameter
1 = ON state,
pr
otective field
free
Speed1 Safety function INT Speed at dynamic con‐
t
rol input 1
-32000 ...
+32000 = speed
in mm/s
Safety-relevant
parameter
Speed1Valid Safety function BOOL Speed1 valid 0 = Invalid speed Safety-relevant
parameter
1 = speed valid
13 TECHNICAL DATA
198