Line Modules Booksize
4.2 Active Line Modules with internal air cooling
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
171
7TE25–5AA3 +
Active Interface
Module
Circuit breaker
(IEC 60947 and UL)
See Section Overcurrent protection using line fuses and circuit
Rated short-circuit current
SCCR
3)
kA 65 65 65 65
Cooling method (internal air cooling)
Max. permissible heat sink
temperature
° C 85 90 83 83
3
Rated voltage for rated data 3 AC 380 V
The specified power ratings apply to the line voltage range from 380 V to 480 V.
Default for 400 V line systems; undervoltage trip threshold is adjusted to the parameterized rated voltage
The resulting rated short-circuit current is obtained from the combination of the fuse or circuit breaker – and the Line
Module in the drive system.
Table 4- 11 Technical data of Active Line Modules
Rated power (S1)
1)
Infeed power (S6 - 40 %)
1)
1)
kW (P
n
)
kW (P
s6
)
max
80
106
120
145
Continuous regenerative power
kW
80
120
Line voltage
Line frequency
V
ACrms
Hz
DC
3 AC 380 … 480 ± 10 % (-15 % < 1 min)
47 … 63
DC link voltage
Overvoltage trip
2)
V
DC
V
DC
510 … 720
820 ± 2 %
Rated input current:
for AC 400 V
Input current:
for AC 380 V / AC 480 V
for AC 400 V; S6 - 40 %
for AC 400 V; peak current
A
AC
A
AC
A
AC
AC
122
128 / 102
161
182
192 / 152
220