Appendix B
B.1 MIB variables of a SCALANCE X300/X400
SCALANCE X-300 / X-400
374 Configuration Manual, 10/2014, C79000-G8976-C187-22
Variables
Access rights
Description
snX300X400StandbyState Read only Displays the standby status:
• 1
Device is master and passive.
• 3
Device is slave and passive
• 5
Device is master and active
• 7
Device is slave and active
• 257
Device searching for partner for standby con-
nection
• 300
The standby function is disabled
• Data type: Integer
snX300X400StandbyStateChan
ges
Read only Indicates how often the standby status was
switched active.
Data type: Counter
snBootStrapVersion Read only The firmware version of the bootloader in the
format
major.minor
.
snHwVersion Read only The hardware version of the system in the format
major.minor
.
snSwVersion
Read only
The software version of the system.
snInfoSerialNr
Read only
The serial number of the product.
snMacAddressBase
Read only
The base MAC address of the IE switch.
snX300X400ModuleIdentMLFB
Read only
The MLFB number of the module.
snX300X400Power
Supply1State
Read only The status of power supply input 1.
snX300X400Power
Supply2State
Read only The status of power supply input 2.
snX300X400ReportDigitalInStat
e
Read only Status belonging to the digital input. (SCALANCE
X414-3E)

Table of Contents

Other manuals for Siemens SCALANCE X-400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SCALANCE X-400 and is the answer not in the manual?

Siemens SCALANCE X-400 Specifications

General IconGeneral
BrandSiemens
ModelSCALANCE X-400
CategorySwitch
LanguageEnglish

Related product manuals