7 Operation at Use of a PC
7.3 Configuration of the Device
121SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Parameterizing an Indication
✧ Select the desired parameters for an indication in the list boxes and option fields as described in
Table 7-4.
✧ You can select the following output types in the Operating mode list box:
Persistent: The binary output has the status ON or OFF. If the indication becomes invalid, the binary
output continues to maintain its current status.
Figure 7-22 Persistent
Persistent with fail save: If the indication becomes invalid, the binary output switches into the OFF
state, that is if Source inverted = no, or it switches into the ON state if Source inverted = yes.
Figure 7-23 Persistent with Fail Save
Pulse without retrigger: This indication is output as pulse. If the indication changes again while the
output pulse is ON, the pulse output time is not restarted. This means that a change of the indication
during the pulse output will be ignored.
Figure 7-24 Pulse without Retrigger
NOTE
If you select -not assigned- as the source of an indication and/or energy counter, the corresponding binary
output is inactive.
invalid
Binary output
inverted
Indication
Indication
Output
Binary output
not inverted
invalid
ON
Output
ON
OFF
OFF
ON
OFF
invalid
Binary output
inverted
Indication
Indication
Output
Binary output
not inverted
invalid
ON
Output
ON
OFF
OFF
ON
OFF
Indication
Output
ON
Binary output with
Source inverted = no
OFF
ON
OFF
Output time
IndicationIndication
Indication
OutputOutputOutput
OutputOutput
Binary output with
Source inverted = yes
ON
OFF
Output time