7 Operation at Use of a PC
7.3 Configuration of the Device
122 SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Pulse with retrigger: This indication is output as pulse. The output pulse is retriggered if the
indication is changed during the pulse output. This means that the pulse output is extended.
Figure 7-25 Pulse with Retrigger
If you have selected one of the two Pulse types in the Operating mode list box, enter an output time x
(in x *10 ms) into the Output time for pulse operating mode field.
Behavior when Activating the Set of Parameters after the Set of Parameters was Changed
Persistent
The binary output is set to the new status (ON or OFF) as defined by the current indication.
Pulse
If the binary output is ON in pulse mode while activating the parameter set, the binary output is
immediately switched to OFF after the parameter set has been activated. This happens even if the
parameterized Output time for pulse operating mode has not yet elapsed.
After the parameterization click Send.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
If you do not want to make any additional settings, continue with the activation of the device configuration
according to section Activating the Set of Parameters. If you want to change other settings, enter the
changes and then enable the device configuration as described in section Activating the Set of
Parameters.
Parameterizing an Energy Counter (see Figure 7-21, for example terminal G1/2)
Enter the desired values into the fields and select the parameter in the list box as described in Table 7-4.
After the parameterization click Send.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
If you do not want to make any additional settings, continue with the Activation of the device configuration
according to section Activating the Set of Parameters. If you want to change other settings, enter the
changes and then enable the device configuration as described in section Activating the Set of
Parameters.
Indication
Output Output with retrigger
Binary output with
Source inverted = no
ON
OFF
ON
OFF
Output time
Output time
IndicationIndicationIndication
Indication
OutputOutput
Output
Output with
retrigger
Binary output with
Source inverted = yes
Extended output time
ON
OFF
Extended output time