Open User Communication
6.11 Secure Open User Communication
Communication
Function Manual, 11/2019, A5E03735815-AH
99
4. Set the parameters for secure communication in the "Start value" column.
"ActivateSecureConn": Activation of secure communication for this connection. If this
parameter has the value FALSE, the subsequent security parameters are irrelevant.
You can set up a non-secure TCP or UDP connection in this case.
"TLSServerCertRef": Enter the value 2 (reference to the CA certificate of the
TIA Portal project (SHA256) or the value 1 (reference to the CA certificate of the TIA
Portal project (SHA1)). If you use a different CA certificate, enter the corresponding ID
from the certificate manager of the global security settings.
"TLSClientCertRef": ID of the own X.509-V3 certificate.
5. Create one of the instructions TSEND_C, TRCV_C or TCON in the program editor.
6. Interconnect the CONNECT parameter of one of the instructions TSEND_C, TRCV_C or
TCON with the tags of the data type TCON_IP_V4_SEC.
Settings at the TLS server
To set up a secure TCP connection in the TLS server, follow these steps:
1. Create a global data block in the project tree.
2. Define a tag of the data type TCON_IP_4_SEC in the global data block.
The example below shows the global data block "Data_block_1" in which the tag "SEC
connection 1 TLS-Server" of the data type TCON_IP_V4_SEC is defined.
Figure 6-20 IP_V4_SEC_Server
3. Set the connection parameters of the TCP connection in the "Start value" column. For
example, enter the IPv4 address of the TLS client for "RemoteAddress".

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals