EasyManuals Logo

Siemens SIMATIC ET 200SP Function Manual

Siemens SIMATIC ET 200SP
362 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #244 background imageLoading...
Page #244 background image
OPC UA communication
9.3 Using the S7-1500 as an OPC UA server
Communication
Function Manual, 11/2019, A5E03735815-AH
243
Subscription with error
If there are too many elements in the queue, there may be an overload of the communication
stack. The CPU cannot check all elements in the given sampling interval and must therefore
skip the next sampling job.
In this case, the CPU sends the status code "GoodOverload" (0x002F0000) per element,
even though the elements were not checked. The meaning of the status code according to
IEC 61131-3 is as follows: "Sampling has slowed down due to resource limitations".
Sampling job is skipped
Figure 9-52 Subscription with error
See also FAQ 109763090.
See also
Settings of the server for subscriptions (Page 181)
Meaning of the "GoodOverload" status
(https://support.industry.siemens.com/cs/ww/en/view/109763090
)
9.3.6.7 Summarizing diagnostics
To prevent the diagnostics buffer being "swamped" by large numbers of identical OPC UA
diagnostics, as of STEP 7 V16 service pack 1, you can set parameters so that these
diagnostics are entered in the diagnostics buffer as group alarm. Per interval (monitoring
time), the CPU then only generates one group alarm per OPC UA diagnostics.
The following sections describe which diagnostics the CPU groups together and how the
process runs with a high message volume.
Requirement
The "Summarize diagnostics in case of high message volume" option is activated in the OPC
UA properties of the CPU (OPC UA > Server > Diagnostics, "Summarize diagnostics" area).
Example
An OPC UA client repeatedly "overloads" an S7-1500 CPU as OPC UA server with a
sampling rate that the server cannot handle (overload).
The "Summarize diagnostics in case of high message volume" setting is activated.
A message appears in the diagnostics buffer for this diagnostic option. It states that the
sampling rate cannot be reached; followed by the number of these events within the
configured interval.

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals