9.5 Tips and recommendations
Communication
284 Function Manual, 11/2019, A5E03735815-AH
9.5 Tips and recommendations
9.5.1 Rules for subscriptions
The following rules apply to subscriptions:
Group subscriptions in the client according to different sampling and publishing intervals
and distribute the monitored elements (variables) to these groups.
Example: Create a subscription for longer publishing intervals (e.g. 5 seconds) and a
subscription for shorter publishing intervals (e.g. 0.1 second).
Disable unneeded subscriptions.
Reason: The "Deactivated" subscription mode reduces resource consumption.
Consider the maximum number of monitored items of subscriptions for the corresponding
S7-1500 CPU.
The information can be found in the technical specification of the respective CPU. The
information is based on a sampling / publishing interval of 1 second.
You can find additional information in the FAQ 109755846
(https://support.industry.siemens.com/cs/us/en/view/109755846
).
Select the same sampling and publishing intervals for the OPC UA client and for the
OPC UA server.
Avoid arrays and structures as elements of subscriptions if the process allows.
Reason: If even one value of an array/structure changes, the entire structure is
transferred, creating an unnecessary communication load.
Occasional non-compliance with the required sampling rate is acknowledged by the OPC
UA server of the S7-1500 CPU according to OPC UA specification with a "GoodOverload"
error code, see also TIA Portal Help. Different OPC UA clients handle "Good" error codes
unequal to "0" differently. Consider this behavior and, if needed, reduce the
communication load according to the measures described above.
See also
Settings of the server for subscriptions (Page 181)

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals