OPC UA communication
9.3 Using the S7-1500 as an OPC UA server
Communication
Function Manual, 11/2019, A5E03735815-AH
181
Backward compatible data type definitions according to OPC UA specification V1.03
The OPC UA specification (<= V1.03) defines mechanisms in order to read out data type
definitions, for example for user-defined structures (UDTs), from a server by means of the
TypeDictionaries.
In the OPC UA server properties of the CPU, you can set whether the CPU generates these
backward compatible data type definitions according to the OPC UA specification V1.03 for
the standard SIMATIC server interface or not.
Because TypeDictionaries are complex and result in large OPC UA XML files (server
interfaces) which the client has to interpret, a simpler solution was introduced with OPC UA
Specification V1.04 (attribute "DataTypeDefinition" at the data type node). If your client
supports the OPC UA specification V1.04 or higher, then disable the option.
Advantages of the data type definitions according to OPC UA specification as of V1.04:
The server starts faster
The memory is used more efficiently
The "Browse" function is faster
9.3.3.4 Settings of the server for subscriptions
Subscription instead of cyclic queries
An alternative to cyclic queries for a PLC tag (polling) is to monitor this value. Use a
Subscription: The server informs the client if the value of PLC tags changes. See "The OPC
UA client".
One server usually monitors a large number of PLC values. For this reason, the server
sends notifications to the client at regular intervals containing the new values of the PLC
tags.
Advantages of subscriptions:
The server starts faster
The memory is used efficiently

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals