OPC UA communication
9.3 Using the S7-1500 as an OPC UA server
Communication
Function Manual, 11/2019, A5E03735815-AH
197
9.3.3.9 Diagnostic settings of the server
Diagnostics
You can specify the scope of the diagnostics of the OPC UA server in the CPU settings.
To change the diagnostics scope, navigate to the "OPC UA > Server > Diagnostics" area.
Figure 9-25 Diagnostic settings of OPC UA server
Default setting
The default setting is a diagnostics behavior that supports the most important diagnostics
without appreciably increasing the communication load.
You enable diagnostics for subscriptions when the OPC UA server also uses subscriptions,
i.e. if necessary during the commissioning phase only.
Reason: A large volume of diagnostic activity generates a high communication load in the
CPU and may suppress other important messages. Or, the high volume of diagnostics may
result in important messages disappearing in the mass of messages and being ignored.
Additional information
You will find additional information on the meaning and effect of the settings shown above
here (Page 233).

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C