EasyManuals Logo

Siemens SIMATIC ET 200SP Function Manual

Siemens SIMATIC ET 200SP
362 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #277 background imageLoading...
Page #277 background image
OPC UA communication
9.4 Using the S7-1500 CPU as an OPC UA client
Communication
276 Function Manual, 11/2019, A5E03735815-AH
"No Security" security policy and authentication via user name and password
You can set the following combination:
Security policy = "No Security" and authentication via user name and password.
The OPC UA server of the S7-1500 supports this combination. OPC UA clients can
connect and encrypt the authentication data or not.
OPC UA client of the S7-1500 CPU also supports this combination: However, in runtime it
only connects if it can send the authentication data encrypted via cable!
Result: With the following configuration, not connection can be established in runtime.
S7-1500 as OPC UA client
OPC UA server which supports no encryption of authentication data when "No Security"
(="none") is set as security policy.
See also
Users and roles with OPC UA function rights (Page 194)
9.4.9.4 Using a configured connection
Introduction
This section shows you how to use a configured connection for OPC UA instructions (third
step).
Requirements
You have created a client interface and added PLC tags and PLC methods to this
interface, see ("First step (Page 251)").
You have configured a connection to an OPC UA server (Second step (Page 268)).
Overview
To read data from an OPC UA server or write data to an OPC UA server, use the following
instructions:
OPC_UA_Connect
OPC_UA_NamespaceGetIndexList
OPC_UA_NodeGetHandleList
OPC_UA_ReadList or OPC_UA_WriteList
OPC_UA_NodeReleaseHandleList
OPC_UA_Disconnect

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals