OPC UA communication
9.2 Security at OPC UA
Communication
156 Function Manual, 11/2019, A5E03735815-AH
9.2.6 Secure transfer of messages
Establishing secure connections with OPC UA
OPC UA uses secure connections between client and server. OPC UA checks the identity of
the communication partners. OPC UA uses certificates in accordance with X.509-V3 from
the ITU (International Telecommunication Union) for client and server authentication.
Exception: A secure connection is not established with the "No security" security policy.
Message security mode
OPC UA uses the following security policies to protect messages:
No security
All messages are unsecured. In order to use this security policy, establish a connection to
a None end point of a server.
Signing
All message are signed. This allows the integrity of the messages received to be
checked. Manipulations are detected. In order to use this security policy, establish a
connection to a Sign end point of a server.
Sign & Encrypt
All messages are signed and encrypted. This allows the integrity of the messages
received to be checked. Manipulations are detected. What is more, no attacker can read
the content of the message (protection of confidentiality). In order to use this security
policy, establish a connection to a "SignAndEncrypt" end point of a server.
The security policies are also named according to the algorithms used. Example:
"Basic256Sha256 - Sign & Encrypt" means: Secure endpoint, supports a series of algorithms
for 256-bit hashing and 256-bit encryption.

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C