OPC UA communication
9.4 Using the S7-1500 CPU as an OPC UA client
Communication
272 Function Manual, 11/2019, A5E03735815-AH
9.4.9.2 Handling of the client certificates of the S7-1500 CPU
Where does the client certificate come from?
If you are using the OPC UA client of an S7-1500 CPU (OPC UA client enabled), you can
create certificates for these clients with STEP 7 V15.1 and higher as described in the
following sections.
When you use UA clients from manufacturers or the OPC Foundation, a client certificate is
generated automatically during installation or upon the first program call. You have to import
these certificates with the global certificate manager in STEP 7 and use them for the
respective CPU.
If you program an OPC UA client yourself, you can generate certificates through the
program. Alternatively, you can generate certificates with tools, for example with OpenSSL
or the certificate generator of the OPC Foundation:
The procedure for OpenSSL is described here: "Generating PKI key pairs and certificates
yourself (Page 153)".
Working with the certificate generator of the OPC Foundation is described here: "Creating
self-signed certificates (Page 152)".
Certificate of the OPC UA client of the S7-1500 CPU
A secure connection between the OPC UA server and an OPC UA client is only established
if the server classifies the certificate of the client as trusted.
Therefore you have to make the client certificate known to the server.
The following sections describe how you can initially generate a certificate for the OPC UA
client of the S7-1500 CPU and then make it available to the server.
1. Generate and export a certificate for the client
For a secure connection you have to generate a client certificate and - if the server and client
are located in different projects - export the certificate.
If client and server are in the same project, exporting the client certificate and subsequent
import are not necessary.
Requirements
The IP interface of the CPU is configured, an IP address is available.
Background: The IP address under which the CPU can be accessed in your system is
entered under "Subject Alternative Name (SAN)".

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals