Communication
Function Manual, 11/2019, A5E03735815-AH
121
Point-to-point link
8
Functionality
A point-to-point connection for S7-1500, ET 200MP and ET 200SP is established via
communications modules (CMs) with serial interfaces (RS232, RS422 or RS485):
S7-1500/ET 200MP:
CM PtP RS232 BA
CM PtP RS422/485 BA
CM PtP RS232 HF
CM PtP RS422/485 HF
ET 200SP:
CM PtP
The bidirectional data exchange via a point-to-point connection works between
communications modules or third-party systems or devices capable of communication. At
least 2 communication partners are required for communication ("point-to-point"). With
RS422 and RS485, more than two communications partners are possible.
Protocols for communication via a point-to-point connection
Freeport protocol (also called ASCII protocol)
Procedure 3964(R)
Modbus protocol in RTU format (RTU: Remote Terminal Unit)
USS protocol (universal serial interface protocol)
The protocols use different layers according to the ISO/OSI reference model:
Freeport: Uses layer 1 (physical layer)
3964 (R), USS and Modbus: Use layer 1 and 2 (physical layer and data link layer;
therefore greater transmission reliability than with Freeport). USS and Modbus use
additionally layer 4.
Properties of the Freeport protocol
The recipient recognizes the end of the data transfer by means of a selectable end
criterion (e.g. character delay time elapsed, receipt of end character, receipt of a fixed
amount of data).
The sender cannot recognize whether the sent data arrived free of errors at the recipient.

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C