Point-to-point link
Communication
122 Function Manual, 11/2019, A5E03735815-AH
Properties of procedure 3964 (R)
When the data is sent, control characters are added (start, end and block check
characters). Make sure that these control characters are not included as data in the
frame.
Connection establishment and termination makes use of control characters.
If transfer errors occur, data transfer is automatically repeated.
Data exchange using Freeport or 3964 (R) communication
The data to be sent is stored in the user program of the corresponding CPU in data blocks
(send buffer). A receive buffer is available on the communications module for the received
data. Check the properties of the receive buffer and adapt them if necessary. You must
create a data block for receiving in the CPU.
In the user program of the CPU, the "Send_P2P" and "Receive_P2P" instructions handle the
data transfer between the CPU and CM.
Procedure for setting up Freeport or 3964 (R) communication
1. Configure an S7-1500 configuration with CPU and CM in the device view of the hardware
and network editor of STEP 7.
2. Select the interface of the CM in the device view of STEP 7.
3. Assign the parameters of the interface (for example connection communication,
configuration of message sending) in the Inspector window of STEP 7 under "Properties"
> "General".
4. Select the "Send_P2P" or "Receive_P2P" instruction in the "Instructions" task card under
"Communication" > "Communications processor" and drag-and-drop the instruction into
the user program (for example into a FB).
5. Assign the parameters for the instructions according to your configuration.
6. Download the hardware configuration and user program to the CPU.
Otherwise: Dynamic parameter assignment of the communications module
In certain types of application it is an advantage to set up communication dynamically; in
other words, program-controlled by a specific application.
Typical applications for this, could be, for example manufacturers of serial machines. To
make the user interfaces as convenient as possible for their customers, these manufacturers
adapt the communications services to the particular operator entries.

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals