OPC UA communication
9.5 Tips and recommendations
Communication
Function Manual, 11/2019, A5E03735815-AH
285
9.5.2 Rules for the user program
User programs for OPC UA
The following rules apply to user programs:
If your application allows it and the communication load is high, you should set a
minimum time for cycle OBs.
Advantages:
The cycle time remains constant for the most part
The CPU has more time for communication tasks throughout
Tip: Use the instruction "Runtime_Info"; mode 21 or mode 25 (see TIA Portal Help) to
analyze the CPU utilization (e.g. communication).
Reduce the number of variables or data blocks that can be reached from OPC UA/HMI.
By default, all variables from OPC UA/HMI are accessible when creating
variables/DBs/IDBs. This measure leads to improved performance when loading in RUN.
Tip: Using the detailed object display in the TIA Portal, you can easily mark the non-OPC-
UA-relevant data blocks as "not accessible from OPC UA".
Consistent transfer of data beyond the limits of simple data types is only possible with
OPC UA methods. If you use other OPC UA functions (Subscriptions, Read/Write), you
must ensure data consistency in the application.
OPC UA offers the "RegisterNodes" service for repeated read and write accesses to the
same variables. Servers can use this service to prepare for optimized access to variables.
The instruction "OPC_UA_NodeGetHandleList" of the S7-1500 as OPC UA client
implicitly calls this service to prepare the server for optimized accesses (in OPC UA
usage "Registered Read/Write").
Calling detailed object display in the TIA Portal
To call up the detailed object display, proceed as follows:
1. Switch to the "PLC Programming" portal in the portal view.
2. Select "Show all objects".

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals