Communication
324 Function Manual, 11/2019, A5E03735815-AH
Communication with the redundant system
S7-1500R/H
13
Introduction
Communication with the S7-1500R/H redundant system basically functions as with the
S7-1500 standard system.
This chapter describes the special features and restrictions for communication with the
S7-1500R/H redundant system.
Communication options for the S7-1500R/H redundant system
Open User Communication via TCP/IP, UDP, ISO on-TCP and Modbus/TCP
S7 communication as server
HMI communication
PG communication
SNMP
Time-of-day synchronization via NTP
Restrictions for communication with the S7-1500R/H redundant system
Open User Communication:
no configured connections
Secure Open User Communication: Not supported, as certificate management is not
possible for the R/H CPUs.
If you have activated Secure OUC, then although you can compile the user program
and load it, you cannot add certificates to the R/H-CPUs.
no FDL connections
Email: The S7-1500R/H CPUs with firmware version V2.6 support the versions < V5.0
of the "TMAIL_C" instruction. Versions from V5.0 are not supported.
No support of connection descriptions according to "TCON_Param"
no OPC UA
no S7 communication as client
no web server
PG communication: It is not possible to access two CPUs online at the same time. You
can either access the primary CPU or the backup CPU.
The CPUs of the S7-1500R/H do not support centrally plugged communication modules.

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals