OPC UA communication
9.2 Security at OPC UA
Communication
Function Manual, 11/2019, A5E03735815-AH
147
Additional security rules
Only use the end point "None" in exceptional cases.
Only use the "guest authentication" of the user in exceptional cases.
Only allow access to PLC tags and DB components via OPC UA if it is genuinely
necessary.
Use the list of trusted clients in the settings of the S7-1500 OPC UA client to allow access
to certain clients only.
9.2.2 Certificates pursuant to ITU X.509
Security mechanisms are integrated in several layers in OPC UA. Digital certificates have an
important role here. An OPC UA client can only establish a secure connection to an OPC UA
server when the server accepts the digital certificate of the client and classifies it as trusted.
See section Handling client and server certificates (Page 183).
The client must also check and trust the certificate of the server. The server and client must
show their identities and prove that they are what they claim to be: They must prove their
identity. Mutual authentication of client and server, for example, prevents man-in-the-middle
attacks.
Man-in-the-middle attacks
A "man-in-the-middle" could have positioned itself between server and client. A man-in-the-
middle is a program that intercepts communication between server and client and claims to
be a client or server, and is thus able to obtain information about the S7 program or to set
values in the CPU and attack a machine or plant.
OPC UA uses digital certificates that meet standard X.509 of the International
Telecommunication Union (ITU).
This allows the identity of a program, a computer or an organization to be proven
(authenticated).

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals