OPC UA communication
9.2 Security at OPC UA
Communication
Function Manual, 11/2019, A5E03735815-AH
149
Signing and encryption
To allow you to check whether a certificate has been manipulated, certificates are signed.
There are various possible procedures here:
Within the TIA Portal you have the possibility to generate and sign certificates. If you have
protected your project and are logged in as a user with the function right to make security
settings, you can use the global security settings. The global security settings allow
access to the certificate manager and therefore to the certificate authority (CA) of the
TIA Portal.
Additional options are available for creating and signing certificates. In the TIA Portal, you
can import certificates into the global certificate manager.
You contact a certificate authority (CA) and have your certificate signed.
In this case, the certificate authority checks your identity and signs your certificate with
the private key of the certificate authority. For this purpose you send a CSR
(Certificate Signing Request) to the certificate authority.
You yourself create a certificate and sign it.
To this purpose you use, for example, the "Opc.Ua.CertificateGenerator" program of
the OPC Foundation. Alternatively, you use OpenSSL.
You can find additional information in Generating PKI key pairs and certificates
yourself (Page 153).
Useful information: Certificate types
Self-signed certificate:
Each device generates and signs its own certificate. Application examples: Static
configuration with limited number of communication nodes.
No new certificates can be derived from a self-signed certificate. However, you need to
load all self-signed certificates from partner devices to the CPU (STOP required).
CA certificate:
All certificates are generated and signed by a certificate authority. Application examples:
Dynamically growing plants.
You only need to download the certificate from the certificate authority to the CPU. The
certificate authority can generate new certificates (partner devices can be added without
CPU STOP).

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals