OPC UA communication
9.3 Using the S7-1500 as an OPC UA server
Communication
232 Function Manual, 11/2019, A5E03735815-AH
Number of implementable server methods and number of arguments
If you implement server methods via your user program, the number of usable methods is
limited depending on the CPU type, see the following table (up-to-date technical data of the
CPUs can be found in the Internet (https://support.industry.siemens.com/cs/ww/en/ps/td
)).
Technical specification value
CPU 1510SP (F)
CPU 1511 (C/F/T/TF)
CPU 1512C
CPU 1512SP (F)
CPU 1513 (F)
CPU 1505 (S/SP/SP F/SP T/SP TF)
CPU 1515 (F/T/TF)
CPU 1515 SP PC (F/T/TF)
CPU 1516 (F/T/TF)
CPU 1507S (F)
CPU 1517 (F/T/TF)
CPU 1518 (F)
Maximum number of usable server
methods or max. number of server
method instances
(OPC_UA_ServerMethodPre,
OPC_UA_ServerMethodPost in-
structions)
20 50 100
Maximum number of arguments
per method
(More than the specified number of
arguments can be configured and
loaded into the CPU, but an OPC
UA client cannot call the method).
20 20 20
Error message when exceeded
If the maximum number of server methods is exceeded, the OPC_UA_ServerMethodPre or
OPC_UA_ServerMethodPost instructions report the error code 0xB080_B000
(TooManyMethods).
Supply of structured data types with nested arrays
If a structured data type (Struct/UDT) contains an array, the OPC UA server does not
provide information about the length of this array.
If you use such a structure as the input or output parameter of a server method, for example,
you must ensure that the nested array is supplied with the correct length when the method is
called.
If you do not adhere to this rule, the method fails with the error code "BadInvalidArgument".

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C