Connection resources
11.3 Display of the connection resources
Communication
Function Manual, 11/2019, A5E03735815-AH
317
The warning triangle in the column of the dynamic station resources is displayed because
the sum of the maximum available connection resources of CPU, CP and CM
(= 310 connection resources) exceeds the station limit of 256.
Note
Available connection resources exceeded
STEP
7 signals the exceeding of the station-specific connection resources with a warning.
To make full use of the connection resources from the CPU, CP and CM, either use a CPU
with a higher maximum number of available st
ation-specific connection resources or reduce
the number of communications connections.
Module-specific connection resources
The columns of the module-specific connection resources provide information about the use
of resources on the CPUs, CPs and CMs of an automation system:
The display is per module and not per interface.
In the example, the CPU makes a maximum of 128 connection resources available, of which
18 are already in use and 110 still available.
The used resources are divided up as follows:
6 resources for HMI communication
4 resources for S7 communication
8 resources for Open User Communication

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals