EIP-200S Ethernet/IP Adapter
2.6 Device profile: supported CIP objects
EIP-200S Ethernet/IP Adapter Distributed I/O System
36 System Manual, 06/2018, A5E44345053-AB
Attribute
ID
Access
rule
Name
Description
Data type
Semantics of values
6 Set Interface
Control
Configuration for physi-
cal interface
STRUCT
of:
See section "Interface
Control" below.
Control Bits
Interface Control Bits
WORD
----
Forced
Interface
Speed
Speed at which the
interface shall be
forced to operate
UINT Speed in Mbps (10, 100,
etc.).
7 Get Interface
Type
Type of interface: twist-
ed pair, fiber, internal,
etc.
USINT
8 Get Interface
State
Current state of the
interface: operational,
disabled, etc.
USINT
10 Get Interface
Label
Human readable idenfi-
cation
SHORT_
STRING
11 Get Interface
Capability
Indication of capabili-
ties of the interface
STRUCT
of:
Capability
Bits
Interface capabilities,
other than
speed/duplex
DWORD Bit map
Speed/Dupl
ex Options
Indicates speed/duplex
pairs supported in the
Interface Control attrib-
ute
STRUCT
of:
Speed/Duplex Array
Count
USINT Number of Elements
Speed/Duplex Array ARRAY
of
STRUCT
of:
Interface Speed USINT Semantics are the same
as the Forced Interface
Speed in the Interface
Control attribute: speed in
Mbps.
Interface Duplex Mode USINT 0 = half duplex
1 = full duplex
2-255 = Reserved

Table of Contents