EasyManua.ls Logo

Siemens SIMATIC S7 EIP-200S - Page 36

Siemens SIMATIC S7 EIP-200S
112 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EIP-200S Ethernet/IP Adapter
2.6 Device profile: supported CIP objects
EIP-200S Ethernet/IP Adapter Distributed I/O System
36 System Manual, 06/2018, A5E44345053-AB
Attribute
ID
Access
rule
Name
Description
Data type
Semantics of values
6 Set Interface
Control
Configuration for physi-
cal interface
STRUCT
of:
See section "Interface
Control" below.
Control Bits
Interface Control Bits
WORD
----
Forced
Interface
Speed
Speed at which the
interface shall be
forced to operate
UINT Speed in Mbps (10, 100,
etc.).
7 Get Interface
Type
Type of interface: twist-
ed pair, fiber, internal,
etc.
USINT
8 Get Interface
State
Current state of the
interface: operational,
disabled, etc.
USINT
10 Get Interface
Label
Human readable idenfi-
cation
SHORT_
STRING
11 Get Interface
Capability
Indication of capabili-
ties of the interface
STRUCT
of:
Capability
Bits
Interface capabilities,
other than
speed/duplex
DWORD Bit map
Speed/Dupl
ex Options
Indicates speed/duplex
pairs supported in the
Interface Control attrib-
ute
STRUCT
of:
Speed/Duplex Array
Count
USINT Number of Elements
Speed/Duplex Array ARRAY
of
STRUCT
of:
Interface Speed USINT Semantics are the same
as the Forced Interface
Speed in the Interface
Control attribute: speed in
Mbps.
Interface Duplex Mode USINT 0 = half duplex
1 = full duplex
2-255 = Reserved

Table of Contents