Commissioning
5.4 Basic commissioning with IOP
Converter with control units CU250D-2
66 Operating Instructions, 04/2014, FW V4.7, A5E34261542B AA
11.
Input the correct Motor Speed from
the motor rating
plate.
This value is given in RPM.
12.
Select to run or disable Motor Data Identification
function.
This function, if active, will not start un
til the first run
command is given to the Inverter.
13.
Select either zero pulse on no zero pulse for the
attached encoder.
If no encoder is fitted to the motor,
the option will not be
displayed.
14.
Enter the correct pulses per revolution for the encoder.
This information is normally printed on the casing of the
encoder
.
15.
Select the macro that is suitable for your application.
Once selected all inputs, outputs, command sources
and setpoints will be automatically configured b
y the
software.
For further information see the section that details the
precise settings for each macro. Please see installation
section of this manual.
16.
Set
the Minimum Speed at which the attached motor
should run.