Controlling the safety functions 
  7.2 Control of "STO" and "SS1" via terminal module for option K82 
Safety Integrated 
Function Manual, 05/2010, A5E03264275A 
125 
Recommended application 
This option is used when: 
●  Activation will be executed optically isolated in a voltage range of 24 V – 230 V DC/AC. 
●  You will be working with non-shielded control lines with lengths greater than 30 m. 
●  The devices will be used in plants with greater spatial elongation (ideal PA not present). 
Functional principle 
Two independent channels of the integrated safety function are activated via the relays (K41, 
K42). 
The relay K41 activates the signal to the control unit that is necessary for the safety function 
and the relay K42 on the Power Module. 
The selection and deselection must be executed concurrently. The time delay that is 
unavoidable due to mechanical switch processes, for instance, can be adapted via 
parameters. 
The circuit is structured so that it is protected against wire break, i.e. if the relay's control 
voltage fails then the safety function is active. 
A checkback signal can be derived for information, diagnostics, or troubleshooting from the 
normally-closed contact switched in series of the relay. Wiring of the checkback signal can 
be executed optionally and is not part of the safety concept. 
 
 
Note 
The checkback signal is not necessary for compliance with the standard DIN EN ISO 13849-
1 (formerly EN954-1) cat. 3 PL d and DIN EN 61508 SIL2. 
 
The selection of the safety function must be executed over two channels. A switch in 
accordance with ISO 13850/ EN 418, positive opening in accordance with EC 60947-5-1, or 
a certified safety controller must be used as activation element.  
 
DANGER 
 
Responsibility for selecting the correct activation element for the purpose of compliance of 
the overall system with the required standard (DIN EN ISO 13849-1 (formerly EN954-1) 
Cat. 3 PL d or DIN EN 61508 SIL2) rests with the user.