Controlling the safety functions
7.5 Control by way of PROFIsafe
Safety Integrated
182 Function Manual, 05/2010, A5E03264275A
Safety Integrated Basic Functions via PROFIsafe and terminals
Control of the Basic Functions via terminals on the Control Unit and on the Motor/Power
Module (parameters p9601.0 = p9801.0 = 1) may be enabled in parallel. In this way, the
STO and SS1 functions (time controlled) can be selected via PROFIsafe telegram 30 as well
as in parallel via the onboard terminals of the Control Unit and Motor Module/Power Module.
STO has priority over SS1, i.e. if SS1 and STO are simultaneously initiated, then STO is
executed.
7.5.3 Structure of telegram 30
7.5.3.1 Structure of telegram 30 (Basic Functions)
PROFIsafe control word (STW)
S_STW1, PZD1 in telegram 30, output signals
See function diagram [2840].
Table 7- 22 Description of the PROFIsafe STW
Bit Meaning Remarks
1 Deselect STO 0 STO
0 Select STO
1 Deselect SS1 1 SS1
0 Select SS1
2 SS2 0
1)
3 SOS 0
1)
4 SLS 0
1)
5 Reserved -
6 Reserved -
1/0 Acknowledgment 7 Internal Event ACK
0 No acknowledgment
8 Reserved -
9 Select SLS bit 0 -
10 Select SLS bit 1 -
1)
11 ...
15
Reserved -
1)
Signals not relevant to Basic Functions should be set to "0".