EasyManua.ls Logo

Siemens SINAMICS S150 - Acceptance Test for Safe Operating Stop (SOS)

Siemens SINAMICS S150
312 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Acceptance test and acceptance report
10.5 Acceptance tests
Safety Integrated
Function Manual, 05/2010, A5E03264275A
279
10.5.2.5 Acceptance test for Safe Operating Stop (SOS)
Table 10- 15 "Safe Operating Stop" function
No. Description Status
Note:
The acceptance test must be individually conducted for each configured control.
The control can be realized via TM54F or via PROFIsafe.
Initial state
Drive in "Ready" state (p0010 = 0)
Safety Integrated Extended Functions enabled (p9601.2 = 1)
Safety functions enabled (p9501.0 = 1)
SOS inactive (r9722.3 = 0)
1.
No Safety faults and alarms (r0945[0...7], r2122[0...7], r9747[0...7]); see note "non-
critical alarms" in section "Acceptance tests".
2. It may be necessary to take measures in the higher-level control to be able to run the drive with activated SOS.
Configure and activate trace recording.
Trigger: Trigger on variable - bit pattern (r9722.7 = 0)
Record the following values: r9713[0], r9720, r9721, r9722
Select the time interval and pretrigger so you can recognize start-up of the drive and
infringement of the SOS tolerance window (p9330/p9530)
For better analysis, display the following bit values:
r9720.3 (deselect SOS)
r9721.12 (STOP A or B active)
r9722.0 (STO active; set for STOP A)
r9722.1 (SS1 active; set for STOP B)
r9722.3 (SOS active)
r9722.7 (internal event; set on the occurrence of the first Safety message)
Select SOS
Run the drive beyond the standstill limit set in p9330/p9530
Check that the drive moves briefly and then decelerates back to a standstill
Check whether the following Safety messages are pending:
C01707, C30707 (Tolerance for safe operating stop exceeded)
C01701, C30701 (STOP B initiated)
3.
C01700, C30700 (STOP A initiated)
Analyze trace:
As soon as r9713[0] (unit µm or m°) leaves the tolerance window, a Safety message
(r9722.7 = 0) becomes active
4.
As a consequence, the drive is brought to a standstill with STOP B and STOP A
5. Save/print the trace and add it to the acceptance report (refer to the example below)
Deselect SOS and acknowledge Safety messages 6.
No Safety faults and alarms (r0945[0...7], r2122[0...7], r9747[0...7])

Table of Contents

Other manuals for Siemens SINAMICS S150

Related product manuals