Commissioning
8.5 Commissioning TM54F by means of STARTER/SCOUT
Safety Integrated
Function Manual, 05/2010, A5E03264275A
205
8.5.4.1 Test stop mode 1
'2
'2
',$*
9H[W
70)
'2
'2
0
$NWRU
Figure 8-6 F-DO circuit, test stop mode 1
Test step
1)
L1+ L2+ Comment
1 OFF ON Synchronization
3 OFF OFF F-DIs 0 ... 4 Check at 0 V
5 ON ON F-DIs 5 ... 9 Check at 0 V
Test step
1)
DO+ DO- Expected response, DIAG signal
6 OFF OFF LOW
8 ON ON LOW
10 OFF ON LOW
12 ON OFF HIGH
14 OFF OFF LOW
Test sequence for test stop mode 1
1)
You can find a complete list of the steps in the SINAMICS List Manual under message F35013.