Acceptance test and acceptance report
10.2 Acceptance test structure
Safety Integrated
Function Manual, 05/2010, A5E03264275A
253
10.2.3 Test scope for specific measures
Scope of partial acceptance tests for specific measures
Table 10- 1 Scope of partial acceptance tests for specific measures
Measure A) Documentation B) Functional testing of
safety functions
C) Functional
testing of forced
dormant error
detection
D) Functional
testing of actual
value acquisition
E) Conclusion
of the report
Replacement of
the encoder
system
No No No Yes Yes
Replacement of an
SMC/SME
Yes, Points 1 and
2
No No Yes Yes
Replacement of a
motor with DRIVE-
CLiQ
Yes, Points 1 and
2
No No Yes Yes
Replacement of
the Control Unit /
power unit
hardware
Yes, Points 1 and
2
No Yes, only Point 1 Yes, only Point 1 Yes
Replacing the
Power Module
Yes, Points 1 and
2
Yes, Points 1 and 3 Yes, only Point 1 Yes, only Point 1 Yes
Replacing the
TM54F
Yes, Points 1 and
2
Yes, but only testing of
the selection of the
safety functions
Yes Yes, only Point 1 Yes
Firmware -
upgrade(CU/power
unit/ Sensor
Modules)
Yes, only Point 2 Yes, if new safety
functions are to be
used
Yes Yes, only Point 1 Yes
Change to a single
parameter of a
safety function
(e.g. SLS limit)
Yes, Points 4 and
5.
Yes, test the
appropriate function
No Yes Yes
Transfer of project
data to other
machines (series
commissioning)
Yes Yes, but only testing of
the selection of the
safety functions
Yes Yes Yes
Note
Forced dormant error detection functional testing (C) and actual value acquisition functional
testing (D) together represent the "simplified function test" mentioned in previous chapters.