Commissioning
8.5 Commissioning TM54F by means of STARTER/SCOUT
Safety Integrated
202 Function Manual, 05/2010, A5E03264275A
8.5.3 TM54F configuration
Configuration screen of TM54F for Safety Integrated
Figure 8-5 TM54F configuration
Functions of this screen:
Assigning drive objects (p10010)
Select a drive object to be assigned to a drive group.
Drive groups (p10011)
Each configured safety drive can be assigned to a drive group using a drop-down list box.
The list box displays the drives and their names.
Discrepancy time (p10002)
The signal states at the two terminals of an F-DI are monitored in order to determine
whether these have assumed the same logical state within the discrepancy time.
Note
The discrepancy time must be set so that it is always smaller than the smallest expected
switching interval of the signal to this F-DI.