System Features
3.5 Response times
Safety Integrated
Function Manual, 05/2010, A5E03264275A
49
3.5.2 Response times, Safety Integrated Extended Functions with encoder
Activation of Extended Functions with encoder via PROFIsafe
The following table lists the response times from receiving the PROFIsafe telegram on the
Control Unit up to initiating the response.
Table 3- 3 Response times when controlling via PROFIsafe
Function Typical Worst case
STO 4 x p9500 + r9780 4 x p9500 + 3 x r9780
SBC
5)
4 x p9500 + 2 x r9780 4 x p9500 + 6 x r9780
SS1 (time and acceleration controlled),
SS2: Call
4 x p9500 + 2 ms
5 x p9500 + 2 ms
SBR, safe acceleration monitoring responds 2 x p9500 + 2 ms 2.5 x p9500 + r9780 + t_DP
1)
SOS standstill tolerance window violated 1.5 x p9500 + 2 ms 3 x p9500 + t_DP
1)
+ 2 ms
SLS speed limit violated
2)
2 x p9500 + 2 ms 3.5 x p9500 + t_DP
1)
+ 2 ms
SSM
3)
4 x p9500 4.5 x p9500 + t_DP
1)
The specified response times involve internal SINAMICS response times. Program run times
in the F host and the transmission time via PROFIBUS or PROFINET are not taken into
account.
Activation of Extended Functions with encoder via TM54F
The following table lists the response times between a signal occurring at the terminals up to
the initiation of the response.
Table 3- 4 Response times with control via TM54F
Function typical Worst case
STO 2.5 x p9500 + r9780 + 1.5 ms 3 x p9500 + 3 x r9780 + 2 ms
SBC
5)
2.5 x p9500 + 2 x r9780 + 1 ms 3 x p9500 + 6 x r9780 + 2 ms
SS1 (time and acceleration controlled), SS2:
Call
2.5 x p9500 + 3 ms
4 x p9500 + 4 ms
SBR, safe acceleration monitoring responds 2 x p9500 + 2 ms 2.5 x p9500 + r9780 + t_DP
1)
SOS standstill tolerance window violated 1.5 x p9500 + 2 ms 3 x p9500 + t_DP
1)
+ 2 ms
SLS speed limit violated
2)
2 x p9500 + 2 ms 3.5 x p9500 + t_DP
1)
+ 2 ms
SSM
4)
3 x p9500 3.5 x p9500 + t_DP
1)