Controlling the safety functions
7.3 Control of "STO" and "SS1" via terminals on the Control Unit and the Motor/Power Module
Safety Integrated
Function Manual, 05/2010, A5E03264275A
143
7.3.1.2 Simultaneity and tolerance time of the two monitoring channels
Simultaneity and tolerance time of the two monitoring channels
The "Safe Torque Off" function must be selected/deselected simultaneously in both
monitoring channels using the input terminals and is only effective for the associated drive.
1 signal: Deselecting the function
0 signal: Selecting the function
"Simultaneously" means:
The changeover must be complete in both monitoring channels within the parameterized
tolerance time.
p9650 SI SGE changeover tolerance time (Control Unit)
p9850 SI SGE changeover tolerance time (Motor Module)
If the "Safe Torque Off" function is not selected/deselected within the tolerance time, this is
detected by the cross-comparison, and fault F01611 or F30611 (STOP F) is output. In this
case, the pulses have already been canceled as a result of the selection of "Safe Torque
Off" on one channel.