Commissioning
8.7 PROFIsafe via PROFINET
Safety Integrated
224 Function Manual, 05/2010, A5E03264275A
8.7 PROFIsafe via PROFINET
8.7.1 Configuring PROFIsafe via PROFINET
The next sections deal with a sample configuration of PROFIsafe communication between a
SINAMICS S120 drive unit and a higher-level SIMATIC F-CPU operating as PROFINET
master.
HW Config can then be used to configure PROFIsafe telegram 30 (sub-module ID = 30) for
the drive objects (abbreviation: DO).
8.7.2 Requirements for PROFIsafe communication
The following minimum software and hardware requirements apply for the configuration and
operation of safety-oriented communication (F communication):
Software:
SIMATIC Manager STEP 7 V5.4 SP4
1)
or higher
S7 F Configuration Pack V5.5 SP3
1)
or higher
S7 Distributed Safety Programming V5.4 SP3
1)
or higher
STARTER V4.1.5 + SSP V4.3 or SIMOTION SCOUT V4.1.5 + SSP V4.3 or higher
Drive ES Basic V5.4 SP4
1)
or higher
Hardware:
A controller with safety functions (in our example, SIMATIC F-CPU 317F-2)
1)
SINAMICS S120 (in our example, a CU320-2)
Correct installation of the devices
1)
When using a SIMATIC F-CPU
NOTICE
If a single software or hardware component is either older than those specified in this
document or is missing, PROFIsafe cannot be configured via PROFIBUS or PROFINET.