Controlling the safety functions
7.2 Control of "STO" and "SS1" via terminal module for option K82
Safety Integrated
128 Function Manual, 05/2010, A5E03264275A
Note
For the following cabinet units (automatic synchronizers), the digital input DI6 of the Control
Unit is also used:
For 3 AC 380 to 480 V:
6SL3710-2GE41-1AAx, 6SL3710-2GE41-4AAx, 6SL3710-2GE41-6AAx
For 3 AC 500 to 600 V:
6SL3710-2GF38-6AAx, 6SL3710-2GF41-1AAx, 6SL3710-2GF41-4AAx
For 3 AC 660 to 690 V:
6SL3710-2GH41-1AAx, 6SL3710-2GH41-4AAx, 6SL3710-2GH41-5AAx
Interconnection in groups
When using a single activation element for multiple cabinet units, the following terminals
have to be used on terminal strip -X41:
-X41:2: Interconnection to the next cabinet unit, terminal -X41:1
-X41:4: Interconnection to the next cabinet unit, terminal -X41:3
-X41:6: Interconnection to the next cabinet unit, terminal -X41:5
-X41:8: Interconnection to the next cabinet unit, terminal -X41:7
-X41:9: Interconnection to the next cabinet unit, terminal -X41:6
Connection of the optional checkback signal to terminal -X41:9
Wiring
The control lines must be permanently laid.
Signal cables and encoder cables should be installed separated from one another.
The shields of the control lines must be wide-area grounded directly after entry into the
control cabinet.
Outside the control cabinet the cables must be laid in such a way that they are safe to walk
on (e.g. as specified in IEC 60204-1).