EasyManua.ls Logo

Siemens SINAMICS S150 - Page 132

Siemens SINAMICS S150
312 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Controlling the safety functions
7.2 Control of "STO" and "SS1" via terminal module for option K82
Safety Integrated
132 Function Manual, 05/2010, A5E03264275A
Load side:
Operational voltage: max. 250 V DC/AC
Rated operating currents:
AC-15 (in accordance with IEC 60947-5-1): 24 - 230 V = 3 A
DC-13 (in accordance with IEC 60947-5-1):
24 V = 1 A
10 V = 0.2 A
230 V = 0.1 A
Min. contact load: 5 V DC, 1 mA at 1 ppm error
Fuse: max. 4 A (fuse weld-free, duty category gL/gG with Ik ≥ 1 kA)
-X41
-K41
14
11
22
21
A1
A2
A1
A2
1234 65
910
78
P
EP +
-K42
12
24
31
32
34
14
11
22
21
24
31
32
12 34
;
;
;
;
;
&RQQHFWLRQWR
;
&RQQHFWLRQWR
;
&RQQHFWLRQWR&8
2SHUDWRUFRQWUROHOHPHQW
)XVH
OLQHVLGH
bWRb9$&bb'&
2SWLRQDOFKHFNEDFN
VLJQDO
)RUZLULQJZLWKWKH
GRZQVWUHDPFDELQHW
Figure 7-2 Circuit terminal module for option K82
A switch in accordance with ISO 13850/ EN 418, positive opening in accordance with EC
60947-5-1, or a certified safety controller must be used as activation element.

Table of Contents

Other manuals for Siemens SINAMICS S150

Related product manuals