Controlling the safety functions
7.2 Control of "STO" and "SS1" via terminal module for option K82
Safety Integrated
Function Manual, 05/2010, A5E03264275A
137
Load side:
Operational voltage: max. 250 V DC/AC
Rated operating currents:
AC-15 (in accordance with IEC 60947-5-1): 24 - 230 V = 3 A
DC-13 (in accordance with IEC 60947-5-1):
24 V = 1 A
10 V = 0.2 A
230 V = 0.1 A
Min. contact load: 5 V DC, 1 mA at 1 ppm error
Fuse: max. 4 A (fuse weld-free, duty category gL/gG with Ik ≥ 1 kA)
-X41
-K41
14
11
22
21
A1
A2
A1
A2
1234 65
910
78
P
EP +
-K42
12
24
31
32
34
14
11
22
21
24
31
32
12 34
&RQQHFWLRQWR
&RQWURO,QWHUIDFH%RDUG;(39
&RQQHFWLRQWR
&8;
&RQQHFWLRQWR
&8;',
2SHUDWRUFRQWUROHOHPHQW
)XVH
OLQHVLGH
bWRb9$&bb'&
2SWLRQDOFKHFNEDFN
VLJQDO
Figure 7-3 Circuit terminal module for option K82
A switch in accordance with ISO 13850/ EN 418, positive opening in accordance with EC
60947-5-1, or a certified safety controller must be used as activation element.
Note
The terminal -X41:10 is permanently connected to the digital input DI7 of the Control Unit.