Controlling the safety functions
7.4 Control via TM54F / option K87
Safety Integrated
Function Manual, 05/2010, A5E03264275A
179
The following signals can be requested by means of p10039[0...3] for each drive group
(index 0 corresponds with drive group 1 etc.):
STO active (power removed)
SS1 active
SS2 active
SOS active
SLS active
3XOVHFDQFHOHG
66DFWLYH
66DFWLYH
626DFWLYH
6/6DFWLYH
'ULYHJURXS[
6DIHVWDWH
S>[@
S>[@
Figure 7-7 Safe state selection
The same signals (high-active) of each drive or drive group are logically linked by means of
AND operation. The different signals selected through p10039 are logically linked by means
of OR operation. Result of these logic operations is the "Safe State" for each drive group.
Each F-DO supports the interconnection of up to 6 signals by way of indexing (p10042[0...5]
to p10045[0...5]) and their output as logical AND operation.
F-DO features
Each F-DO with fail-safe configuration consisting of two digital outputs plus one digital
input for checking the switching state for forced dormant error detection
Status parameters r10052/r10053
Function diagrams
2853 TM54F (F-DO 0 ... F-DO 3, DI 20 ... DI 23)
2856 TM54F Safe State selection
2857 TM54F assignment (F-DO 0 ... F-DO 3)