Acceptance test and acceptance report
10.5 Acceptance tests
Safety Integrated
266 Function Manual, 05/2010, A5E03264275A
No. Description Status
r9772.0 = r9772.1 = 0 (STO deselected and inactive – Control Unit)
r9872.0 = r9872.1 = 0 (STO deselected and inactive – Motor Module)
r9773.0 = r9773.1 = 0 (STO deselected and inactive – drive)
r9774.0 = r9774.1 = 0 (STO deselected and inactive - group); only relevant for grouping
r0046.0 = 1 (drive in "switch-on inhibit" state)
Acknowledge "switch-on inhibit" and run the drive. Ensure that the correct drive is running. 4.
The following is tested:
Correct DRIVE-CLiQ wiring between Control Unit and Motor/Power Modules
Correct assignment of drive No. – Motor/Power Module – motor
The hardware is functioning properly
Correct wiring of the switch-off signal path (only via terminal)
Correct assignment of the terminals for STO on the Control Unit
Correct STO grouping (if available)
Correct parameterization of the STO function
Forced Checking Procedure of the Shutdown Paths