EasyManua.ls Logo

Siemens SINAMICS S150 - Page 274

Siemens SINAMICS S150
312 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Acceptance test and acceptance report
10.5 Acceptance tests
Safety Integrated
274 Function Manual, 05/2010, A5E03264275A
Example Trace SS1 with encoder
'HVHOHFW66
'ULYHBU>@6,0RWLRQGLDJQRVWLFVVSHHGFXUUHQW6%5VSHHGOLPLWRQ&RQWURO8QLW
%LWWUDFNV
'ULYHBU>@6,0RWLRQGLDJQRVWLFVVSHHGDFWXDOORDGVLGHVSHHGYDOXHRQ&RQWURO8QLW
66DFWLYH
672DFWLYH
Figure 10-1 Example Trace SS1 with encoder
Trace evaluation:
SS1 function is selected (time axis 0 ms; see bit "deselection SS1")
Response bit "SS1 active" is set (time axis approx 20 ms)
The drive decelerates along the configured OFF3 ramp (p1135)
Recording of r9714[0] (orange curve) shows whether the OFF3 ramp is active
STO is activated (time axis approx. 370 ms; see bit "STO active"); at this point the speed
underranges the shutdown speed SS1 (p9560/p9360) (in this case shutdown speed SS1
is underranged before SS1 timer p9556/p9356 has expired)
Brown curve: Envelope curve of function SBR (r9714[1]); a fault is generated if this is
exceeded by the actual speed (r9714[0])
Note
Minor time differences (of the order of 2 to 3 Safety clock cycles (here up to 36 ms)) are
caused by internal calculations and do not present a problem.