Acceptance test and acceptance report
10.5 Acceptance tests
Safety Integrated
284 Function Manual, 05/2010, A5E03264275A
Trace evaluation:
SLS function with SLS level 1 is active (see bits "deselection SLS", "selection SLS bit 0",
"selection SLS bit 1" and "SLS active", "active SLS level bit 0" and "active SLS level
bit 1")
Drive is accelerated beyond the SLS limit (time axis from approx. -400 ms)
Exceeding of the limit is recognized (time axis 0 ms)
Safety fault is initiated (time axis 0 ms; bit "internal event" is set to 0)
Fault response STOP A is initiated (time axis 0 ms; see bit "STOP A or B active" and
"STO active")
Drive coasts (see orange curve of r9714[0])
Note
Minor time differences (of the order of 2 to 3 Safety clock cycles (here up to 36 ms)) are
caused by internal calculations and do not present a problem.